CJ520404 Rev. C
8/10 2 of 2
©1994, 2010 Acuity Brands Lighting, Inc.
All Rights Reserved.
Non-Flexible Wiring Method
If non-flexible wiring method is used, follow
procedure for flexible wiring method. Then
lower mounting frame equal to the thickness
of the finished ceiling or slightly above as
shown in Figure 4.
3. Remove knockouts on junction box to feed
power supply to fixture as shown in Figure 5.
Supply wire must meet applicable electrical
codes and be rated for a minimum for 90°C.
Junction box is thru-wire rated for 8-No. 12
AWG conductors (4in-4out).
4. Complete necessary splices. Snap the door
onto the junction box as shown in Figure 5. If
the ballast is desired on the opposite side of
the junction box, pass the entire door and
ballast assembly through the junction box
and snap into place.
5. Drop socket housing assembly through
mounting frame opening.
Figure 4
Ceiling
Mounting
Frame
Reflector
Junction Box
Figure 5
INSTALLATION INSTRUCTIONS - GRSF L/YK MOUNTING FRAME
Comentarios a estos manuales